Solution
Description
———— Product Features ————

- This product series is an industrial-grade offering designed to meet industrial‑grade standards.
- It adopts a plug-and-play modular design.
- Based on LDC’s proprietary inverter magnetic parallel‑connection patent technology, unlimited‑unit parallel redundancy operation has been achieved.
- Selecting a configured power equipment lifecycle management system enables fault detection, automated fault remediation, and lifespan prediction for the equipment.
- This product series comprises only three‑phase input, single‑phase output models.
- A standalone system can be configured to achieve virtually unlimited capacity,
- Single-phase UPS power module capacities: 2, 3, 5, 6, 7.5, and 10 kVA at 220 V DC; or 1.5, 2, 3, 4, and 5 kVA at 110 V DC.
———— Application Industries ————

Smart Substation for Nuclear Power Plants

Smart Substation for Oil & Gas

Petrochemical Smart Substation

Intelligent Substation for the Coal Chemical Industry

Smart Substation for the Chemical Industry

Other industrial applications
———— Advantages of the MPR Module ————

Professional design tailored to China’s power grid environment.

Input-output dual-isolation transformer design, input,
DC, with complete electrical isolation among the three output terminals, over-
Extremely high carrying capacity and strong anti-interference capability.

Designed and manufactured to industrial-grade standards, significantly enhancing…
of the system’s reliability

Two-stage phase-locked loop with automatic tracking and complete generator synchronization
Compatible

Special five-stage overload protection, better suited for various types.
of the load

Comprehensive protection features: overload, overtemperature, and output.
Short circuit, low battery voltage, high battery voltage, module
All can automatically log out and disconnect from the system.

International standard communication protocols and interfaces: MODBUS and
RS485
———— Technical Specifications ————

Each module has a capacity of 2, 3, 5, 6, 7.5, or 10 kVA (DC 220 V), and 1.5, 2, 3, or 4,
5 kVA (DC 220 V) can be directly and infinitely paralleled.

DC input voltage for each module: 96, 110,
192, 220V, or customized per customer requirements

The system can accept two distinct AC power inputs:
Working power supply, bypass power supply

It can operate in N+1 redundancy mode or in capacity‑expansion mode.

Provides an RS232 interface and includes open communication protocols.
Protocol and monitoring software. An RS485 interface is available as an option,
Standard protocols, such as MODBUS, are available.

Inverter fault, bypass fault, battery fault, utility power
Abnormality, overload, comprehensive fault, utility mode, direct
Flow mode, bypass mode; other contacts can also be selected.
Type

Provides a large-screen LCD with Chinese-language display.
———— Performance Features ————
01.
Modularization
Using 1.5–6 kVA power modules as a single unit, they can be directly and infinitely paralleled.
02.
Flexibility
The UPS capacity can be flexibly increased or decreased as needed.
03.
Redundancy
N+X redundancy can be implemented as needed to maximize system reliability.
04.
Hot-swappable backup feature
In any situation, you can easily replace modules without shutting down the UPS—providing uninterrupted protection for your equipment even during battery operation, maintenance, or capacity upgrades.
05.
Reliability
Any single point of failure will not affect the operation of the entire system.
06.
Capacity expansion issue
It can be flexibly scaled to meet users’ actual needs.
07.
Maintainability issues
Users can perform repairs themselves, without the need for professional technicians.
———— Product Principle Block Diagram ————


Principle of Non-Rechargeable Systems


Schematic Diagram of the Charging System
———— Product Specification Sheet ————
| Rated output power | 2~3 kVA | 4~6 kVA | 7~10 kVA | |||
| Output power factor | 0.8 | |||||
| Technology Type | Online double-conversion | |||||
| Design Technology | Input and output isolation transformer design, multi-CPU redundancy design | |||||
| Structure | Modular and parallelizable | |||||
| Parallel Operation Settings | Shared load, redundant parallel operation technology | |||||
| Redundancy n+1 | The standard number of parallel units is eight; the number of paralleled units can be increased upon customer request. | |||||
| Capacity expansion | Increase according to user electricity demand | |||||
| Double-conversion AC-to-AC efficiency | 85% | |||||
| Noise at 100% load | 50dBA | |||||
| UPS ambient temperature | -30~+40℃ | |||||
| Storage temperature | -30~+70℃ | |||||
| Heat dissipation | Forced air cooling, fan-based heat dissipation | |||||
| Relative temperature | <95% (non-condensing) | |||||
| Standard | EN 50091, Parts 1, 2, and 3 | |||||
| Maintenance | Perform maintenance work from the front side. | |||||
| Positioning | At least 10 cm of clearance must be left at the rear. | |||||
| Input/output cable | Terminal block connection, bottom wire entry | |||||
| Dry contact | Multiple dry contacts are available for automation use. | |||||
| Smart Interface | For network management and monitoring | |||||
| UPS module weight | 50kg | 90kg | 110~150kg | |||
| UPS power module dimensions | 483 x 178 x 530 mm (4U, including tray height) | 483 x 356 x 530 mm (8U, including tray height) | 483x534x530mm (12U including tray height) | |||
| 583 x 178 x 430 mm (4U height including tray) | 583 x 356 x 430 mm (8U, including tray height) | 583x534x430mm (12U including tray height) | ||||
———— Rectifier Parameters ————
| Input voltage | Single-phase 220 V / 230 V / 240 V, three-phase 380 V / 400 V / 415 V | |||||
| Input voltage range | +/-25V(%) | |||||
| Input frequency | 45-55HZ | |||||
| Input power factor | 0.85 | |||||
| Impulse current | Subject to software launch restrictions | |||||
———— Inverter Parameters ————
| Rated output power | 2~3 kVA | 4~6 kVA | 7~10 kVA | |||
| Rated output voltage | Single-phase 220V/230V/240V | |||||
| Output power factor | 0.8 | |||||
———— Output voltage range ————
| Static | +/-1% | |||||
| - Load step change (0–100%, 100–0%) | +/-5% | |||||
| -Linear load distortion factor | +/-2% | |||||
| - Nonlinear load distortion factor | ±3% (compliant with EN 50091-1) | |||||
| Recovery time after a load step change (0–100%, 100–0%) | 20msec | |||||
| Output waveform | Sine wave | |||||
| Output frequency | 50 or 60 Hz | |||||
———— Output frequency range ————
| Free operation | +/-0.1%Hz | |||||
| When synchronized with the utility grid (adjustable) | +/-5%Hz | |||||
| Overload capacity | 125 for 10 minutes, 150 for 1 minute | |||||
| Peak factor | 3:1 (customizable to a crest factor greater than 3:1) | |||||
———— DC parameters ————
| Battery voltage | 96/110/192/220VDC | |||||
| Voltage range | +/-20% | |||||
———— Configure cabinet specifications ————
| Standard cabinet | MPRC168 | MPRC186 | MPRC268 | MPRC286 | MPRC386 | MPRC386 |
| Rack configuration allowed | Six 4U or three 8U power modules | 3 × 8U or 6 × 4U power modules | 4 × 8U or 8 × 4U power modules | |||
| 1 set of manual bypass switch | 1 set of manual bypass switch | 1 set of manual bypass switch | ||||
| 1 set of standard 8-channel AC outputs | 1 set of standard 8-channel AC outputs | No AC distribution output | ||||
| Standard cabinet configuration | Cabinet body, input isolation transformer (optional), terminal block, modular plug-in terminals, cooling fan, and other components. | |||||
| Maximum power rating | 18KVA/14.4KW | 18KVA/14.4KW | 24KVA/19.2KW | |||
| Dimensions (mm): Width x Height x Depth | 600x1800x800 | 600x2000x800 | 800x2000x600 | 600x2260x800 | 800x2260x600 | |
| Weight (kg) | 100 | 120 | 140 | |||
Related products