SRE Series DC Power Supplies
Dynamic adaptation, easy height adjustment, and self-healing.
Monitoring content is automatically generated based on the monitored object.
Supports multiple bus options, including CAN bus.
Dynamic Adaptive Monitoring Technology
Customize monitoring content based on user requirements.
The configuration table adopts an import-based configuration mode, supporting multiple configuration methods, both offline and online.
Automatically generate real-time system diagrams and other human-machine interfaces based on the system configuration.
Dynamically generate IEC 61850 protocol model files based on system configuration.
The integrated power system monitoring and the subsystem monitoring serve as redundant backups for each other.
The system is freely customizable and wirelessly scalable.
Communication Technology
Built-in IEC 61850 communication protocol;
The communication logic model is fully compliant with the DL/T 329 standard.
Multi-mode network time synchronization;
Fiber-optic communication and dual-network redundancy design;
Description
1. When configuring subsystem monitoring, it can be set up in a redundant configuration with the subsystem monitoring system.
2. Without any subsystems, the system can independently perform comprehensive parameter monitoring for substations of all voltage levels, ranging from 10 kV to 750 kV.
3. Modular configuration technology;
4. A fully customized human-machine interface tailored to the system configuration;
5. The display interface size can be customized to suit different substation levels;
6. High-resolution, high-brightness true-color industrial-grade TFT touchscreen;
7. Equipped with multiple communication interfaces, including USB, Ethernet, RS232/485, and CAN.
8. Low-level CAN bus communication;
| SER-M-10 System Monitoring | |
| Supply voltage | DC24V |
| Supply current | ≤1.5A |
| Product Configuration | Clock speed: 400 MHz |
| 64 MB of memory | |
| 128 MB of memory | |
| 10.4-inch screen | |
| Attached interface | 2 RS485 interfaces, 1 CAN interface, 1 100 Mbps Ethernet port, 1 USB host port, and 1 USB device port. |
| Product dimensions | 315×239×56mm |
1. It can measure the voltages of two incoming feeders, busbar voltage and current, the status of input circuit breakers, busbar tie‑breaker status, ATS status, lightning protection status, and more.
2. Can monitor the status signals of 16 feeder circuits;
3. It can be connected to a three-phase energy meter to acquire busbar input power, power factor, frequency, and various electrical energy quantities.
4. Supports six operating modes, with automatic or manual control of ATS operation;
5. It features multiple protection functions, such as overload protection and ground fault protection, among others.
6. Built-in real-time clock with 1 ms resolution for recording event timestamps;
7. Interlocking switching prevents fault propagation;
| SER-ATS-10 Incoming Line Monitoring Unit | |
| Supply voltage | DC 80-320V AC 80-264V |
| Supply current | ≤0.1A |
| Detection volume | Two incoming line voltages, busbar voltage and current, zero-sequence current, 32 digital input channels, 21 relay output channels, 8 DIP switches, and an electric energy meter interface. |
| Communication port | 2-channel RS485 interface |
| CAN bus interface for Line 1 | |
| Size | 424×200×55mm |
1. Comprehensive power supply parameter management
2. A single module integrates functions for discrete signal detection, insulation monitoring, and current measurement.
3. Simultaneously monitors the trip status of 16 feeder circuits, switch statuses, and current/leakage current.
4. Compatible with feeder monitoring for power supplies, communication power supplies, and inverter power supplies.
5. Supports parallel operation and can be scaled infinitely.
| SRE-K-10 Feeder Monitoring Unit | |
| Supply voltage | DC 80-320V AC 80-264V |
| Supply current | ≤0.1A |
| Detection volume | 32 digital input channels, 16 analog input channels, and 8 DIP switches. |
| Communication port | RS485 interface, Route 1 |
| CAN bus interface for Line 1 | |
| Size | 299×138×55mm |
| SER-DC-10 DC Monitoring Unit | |
| Supply voltage | DC 80-320V AC 80-264V |
| Detection volume | 8-channel digital input, 8-channel relay output, 8-channel analog input, 8-channel DIP switch, 1-channel temperature signal |
| Communication port | RS485 interface, Route 1 |
| CAN bus interface for Line 1 | |
Technical Features |
It can detect the status of 8 digital input channels and control the output of 8 relay contacts. |
| It can measure the busbar voltage and current, as well as the control busbar and battery voltage and current, and it can also assess the insulation condition of the busbar. | |
| Can detect the temperature status of a single channel. | |
| R22010F/20F/30F Rectifier Module | ||||
| Technical Specifications | Voltage regulation accuracy | ≤0.5% | Steady-flow accuracy | ≤0.5% |
| Conversion efficiency | ≥94% | Audible noise | ≤55db | |
| Ripple factor | ≤0.1% | Current sharing degree | ≤3% | |
| Features | CAN bus communication technology, full‑range soft‑switching technology | |||
| Technical Features | Input | 380V±15%, 50HZ±10% | ||
| Output | 10A-30A/230V(180V-286V) | |||
| Cooling method | Smart Air Cooling | |||
Related products