Solution

Description

———— Product Features ————

  • This product series is an industrial-grade offering designed to meet industrial‑grade standards.
  • It adopts a plug-and-play modular design.
  • Based on the U.S.-originated LDC inverter magnetic parallel‑connection patent technology, it enables unlimited‑unit parallel redundancy operation.
  • Selecting a configured power equipment lifecycle management system enables fault detection, automated fault remediation, and lifespan prediction for the equipment.
  • This product series comprises two models: three-input single-output and three-input three-output.
  • The maximum capacity of a standalone system can reach 2.5 MVA.
  • Single-phase UPS power module capacities: 10 kVA, 20 kVA, 30 kVA, 40 kVA, 60 kVA, 100 kVA, 125 kVA, 200 kVA, 250 kVA.
  • Three-phase UPS power module capacities: 10 kVA, 20 kVA, 30 kVA, 40 kVA, 60 kVA, 100 kVA, 125 kVA, 200 kVA, and 250 kVA.

———— Application Industries ————

It is primarily used in distributed‑power supply applications on production lines, as well as in centralized power‑supply settings such as DCS control systems, communication systems, monitoring systems, and network management centers—critical equipment and environments that require highly reliable, uninterrupted power.

Coal chemical industry

Oil & Gas (Onshore, Offshore Platforms, Pipelines, Refining, Floating Production Storage and Offloading)

Petrochemicals (onshore, offshore platforms, pipelines, refining, floating production storage and offloading)

Nuclear power, concentrated solar power, hydrogen energy, and other new energy sources

New materials, semiconductors, and other strategic emerging industries

Other industrial applications

———— Technical Specifications ————

It is primarily used in distributed‑power supply applications on production lines, as well as in centralized power‑supply settings such as DCS control systems, communication systems, monitoring systems, and network management centers—critical equipment and environments that require highly reliable, uninterrupted power.

The rectifier employs 12-pulse, 18-pulse, or 24-pulse SCR-based rectification, while the inverter utilizes IGBT-based inversion.

32-bit DSP all-digital control technology

Parameter control and settings can be configured via software.

ABM fast-charging design, configurable via the control panel.

Input power factor as high as 0.90

Multi-unit infinite parallel redundancy system

Extremely high overall machine efficiency

Input current distortion below 7%

International Standard Communication Protocol

———— Performance Features ————

It is primarily used in distributed‑power supply applications on production lines, as well as in centralized power‑supply settings such as DCS control systems, communication systems, monitoring systems, and network management centers—critical equipment and environments that require highly reliable, uninterrupted power.

01.

Fully modular design

“Plug-and-Play” modular design (divided into SDP and MDP series): the rectifier unit, inverter unit, and isolation diodes are integrated into a single module, enabling easy plug‑and‑play replacement and significantly reducing maintenance time.

02.

Fully redundant design

Multiple power modules operate in parallel, achieving N+1 redundancy. The control power supply, the microprocessor on the main control board, and the cooling fans all feature dual-redundant designs, ensuring that a single thermal or electrical failure will not compromise system operation. Output voltage regulation employs a 1+1 redundant closed-loop control scheme, guaranteeing that even if one feedback path fails, no overvoltage will be generated to damage the load.

03.

Multi-language LCD display (Chinese, English, Russian, Spanish)

Large-screen LCD display, UPS monitoring software with multi-language support, simple and intuitive operation, no language barriers, and easy to learn.

04.

Fully digital control

Employing control switching components such as DSPs and IGBTs: ensures system stability and enhances mechanical efficiency.

05.

Intelligent Parallel Hot Backup

No paralleling board is required; a single communication cable suffices to enable multiple hosts to operate in parallel with redundancy. The communication cables between the parallel hosts are arranged in a ring topology, forming a closed loop—so even if one cable is severed, it does not disrupt multi‑stage parallel operation.

06.

Human-centered control design

There are no rigid procedural restrictions; operation is straightforward, unlike other brands of UPS that impose strict operating‑procedure constraints.

07.

Ultra-wide input voltage range

Under full-load conditions, the input voltage range is exceptionally wide—300 VAC to 520 VAC—and even when most UPS systems rely on battery discharge to maintain stable output voltage, these units can still operate as usual.

08.

Intelligent detection and speed control of cooling fans

Any fan malfunction can be monitored via the UPS panel or through the RS‑232 interface. The fan speed automatically adjusts according to the load, extending the fan’s service life and reducing noise.

09.

The static switch has an extremely short switching time, enabling seamless, disturbance-free switching.

Employing 32-bit DSP digital control technology and a current‑mode detection method, the switching time is reduced to 0.

10.

Data recording capability

All data and timestamps associated with abnormal conditions are stored in the UPS, enabling users to clearly monitor any issues that arise. Even during a power outage, the data retained in the UPS remains intact.

11.

Remote Diagnosis and Testing

Remote diagnostics and testing of multiple UPS systems are available via the Internet, ensuring your system operates at peak reliability at all times.

12.

Intelligent Communication Interface

One RS‑232 port, four RS‑485 ports, and standard communication protocols comprise the intelligent monitoring system. It also supports SNMP devices for remote network management. More than 20 pairs of passive dry contacts are available for flexible configuration and use.

———— Product Principle Block Diagram ————

Block Diagram of the Industrial-Grade Three-Phase Input, Single-Phase Output SDP System

Principle Block Diagram of an Industrial-Grade Three-Phase Input/Three-Phase Output SDP System

———— Product Specification Sheet ————

Model number SDP SDP SDP SDP SDP SDP SDP
10 15 20 30 40 50 60 80 100 120 160 200 250~300 350~ 400 450~ 500 600~1080
UPS type Double isolation, double conversion online type
Efficiency >92%
UPS ambient temperature -30~+50℃ (customizable within this temperature range to suit the environmental conditions of each country)
UPS storage temperature -30~+70℃
Relative humidity <95% (non-condensing)
Height <2000 m (above sea level)
Power derating at altitudes above 1500 m 7%/km
Ventilation method 1+1 redundant fans, forced air cooling, top-and-bottom airflow
Noise <60dBA <80dBA
Input/Output Cable Connection Bottom or top (optional)
Communication interface RS232 (1 port) / RS485 (4 ports) / Dry contacts (1 set of 15 pairs), (SNMP optional)
Standardization CE, EN 50091-1,2 Compliant with
FCC CLASS A Compliant with
Protection circuit Short-circuit protection Rectifier/Backup Power Supply/Bypass Switch
Lightning Protection MOV
EMC protection Input & Output
Quarantine Full isolation for input, output, and bypass

 

———— Rectifier ————

Bridge rectifier Three-phase 6-pulse controlled rectifier Three-phase 12-pulse controlled rectifier Three-phase 18-pulse controlled rectifier Three-phase 24-pulse controlled rectifier Three-phase 30-pulse controlled rectification Customizable for more than 36 pulses.
Input isolation transformer Standard configuration
Rated Input Voltage (VAC) 3*190V/200V/208V/220V/230V/380V/400V/440V/460V/480V/500V/525V/600V/660V/690V
Input voltage range -40%+35%
Input frequency 50/60Hz±10%
Input power factor >0.9 >0.95 >0.98
DC output voltage 110VDC/216VDC/360VDC/384VDC
DC output voltage accuracy (with load varying from 0% to 100%) 110VDC/216VDC/360VDC/384VDC±1%
Efficiency 99%

 

———— Inverter ————

Bridge inverter IGBT inverter with DSP control
Output isolation transformer Standard configuration
DC input range 110VDC/216VDC/360VDC/384VDC±25%
Rated output voltage Single-phase: 110V/115V/120V/127V/130V/220V/230V/240V/254V/265V/277V/288V/300V/345V/380V/400V
Three-phase (line voltage): 190V/200V/208V/220V/230V/380V/400V/415V/440V/460V/480V/500V/525V/600V/660V/690V
Number of output phases Single-phase, three-phase
Output power factor 0.8
Output frequency 50/60Hz±0.1%
Output voltage stability Static ±1%
Dynamic
(0~100%~0)
±3%
Output voltage recovery time After a step load, it recovers to within ±2% within 1 millisecond.
Overload capacity 125% for 10 minutes, 150% for 1 minute.
Short-circuit characteristics Short-circuit protection, current limiting at 3 times the rated current, 100 ms
Output waveform Sine wave
Output waveform distortion Linear load <2%
Nonlinear load (crest factor 3:1) <5%
Peak factor 3:1 (customizable to a crest factor greater than 3:1)
Efficiency >93.5%
DC Cold Start Can do.

 

———— Bypass ————

Automatic Static Switch Thyristor SCR, (redundant design optional)
Rated voltage 220V/230V/240V/380V/400V/415V ±20% (adjustable)
Rated frequency 50/60 Hz ± 5% (adjustable)
Static bypass transfer time 0ms
Inverter to Static Bypass Inverter testing, inverter fault, excessive inverter input voltage, excessive inverter output voltage
Overload capacity 1.5 30min
10 1min

 

———— Mechanical Parameters ————

Model number SDP SDP SDP SDP SDP SDP SDP SDP SDP
10 15 20 30 40 50 60 80 100 120 160 200 250~300 350~ 400 450~ 500 600~1080
Protection rating IP20, IP21, IP30, IP32, IP40, and IP42 are available; other options can be custom‑made.
W 600 800 1200 1800 2400 3000 4800 6000 Customizable
D 800
H1 1800 (IP20, IP30, IP40)
H2 2000 (IP21, IP32, IP42)
Weight (kg) 700~1000 1100-2000 2500-3000 3500-4000 4500-5000 5500-6000 >6000

Related products